Characterization of clamp-on current transformers under nonsinusoidal conditions
2009
This paper reports the performance of clamp-on current transformers under nonsinusoidal conditions. A set of experimental measurements helped to determine the ratio and the phase errors under two conditions: 1) sinusoidal excitation with frequencies from 45 to 1000 Hz and 2) nonsinusoidal excitation using the fundamental frequency and one harmonic, with adjusted phase shift. It was found that ratio and phase errors are affected by the phase angle between the harmonic and the fundamental and the harmonic amplitude. The effects of conductor location in the current transformer's window and of the air-gap width were also investigated. It was concluded that harmonic phase and ratio errors measur…
A new low cost power line communication solution for smart grid monitoring and management
2018
Modern smart grids require the improvement of measurement and communication infrastructures of distribution networks, at both medium voltage (MV) and low voltage (LV) levels. Distributed sensing and measurement systems are needed to provide all necessary data for grid monitoring, control and management, as well as for the implementation of a number of smart functionalities, such as remote control of distributed generators (DGs), real time analysis of power flows, automatic meter reading (AMR), demand side management (DSM), grid automation and so on [1]-[6]. Acquired network data include typical electrical network quantities and status variables (such as powers, voltages, currents, switches …
A novel approach to current transformer characterization in the presence of harmonic distortion
2009
The current transformer (CT) performance under distorted waveform conditions is usually characterized by means of the frequency-response test. In this paper, a new way to characterize CTs, closer to real operation conditions, is proposed. The harmonic phase-angle and ratio errors are measured using a nonsinusoidal current composed of fundamental and one harmonic with adjustable phase shift. The new method was tested by determining the performance of two metering class CTs commonly used by the Italian power company. The errors measured using the proposed approach are larger than the ones obtained with the frequency response. This result suggests that the frequency-response approach for the e…
Measurement uncertainty impact on simplified load flow analysis in MV smart grids
2018
This work is focused on the measurement uncertainty impact on load flow analysis in medium voltage (MV) distribution networks. In more detail, the paper presents the uncertainty evaluation of a simplified load flow algorithm, which is based on the load power measurements at each secondary substation and one voltage measurement at the slack bus (i.e. the voltage at the MV bus bars of the primary substation). To reduce the costs of the monitoring system, the load flow algorithm makes use of LV load power measurements for all the substations except those of MV users, where MV transducers are usually already installed. The uncertainties on the algorithm input quantities (load powers and slack b…